MOXA ICF-1171I Series

Industrial CAN-to-fiber converters for distance extension

MOXA ICF-1171I Series
7849_33939.png
7849_33940.jpg
7849_33941.jpg
  • Les caractéristiquesLes caractéristiques
  • PrésentationPrésentation
  • Plus d'informationPlus d'information
  • PDFPDF
  • Transmits data for up to 40 km over optical fiber
  • Converts CAN signals to fiber and vice versa
  • Supports CAN 2.0A, CAN 2.0B, and CAN FD; conforms with the ISO 11898 standard
  • CAN 2.0 supports auto-baudrate
  • CAN 2.0 arbitration rate up to 1 Mbps
  • CAN FD arbitration rate up to 1 Mbps; data rate up to 5 Mbps
  • Dual power inputs for redundancy
  • Wide-temperature model available for -40 to 75°C environments
  • DIP switch for 120-ohm terminal resistance
  • Rotary switches for CAN 2.0/CAN FD arbitration and data rate configuration
  • LEDs for CAN bus diagnostics, fiber diagnostics, and power input status
The ICF-1171I Series CAN-to-fiber converters are used in pairs to connect two CAN 2.0 or two CAN FD devices or networks via single-mode or multi-mode optical fiber. The ICF-1171I provides 2-kV isolation protection for the CAN interface and dual power inputs to ensure that your CANbus system will work uninterrupted.


Extend the CAN Bus Transmission Distance

The total transmission distance of a CAN 2.0 or CAN FD system can be extended by 2 km (multi-mode fiber) or by 40 km (single-mode fiber) using ICF-1171I converters, regardless of the CAN baudrate.


Easily Fulfil Various Communication Scenarios

Two CAN 2.0 networks or CAN FD networks can communicate with each other using different baudrates. The ICF-1171I converters can automatically detect the baudrate of the connected CAN 2.0 device and apply the baudrate to itself. Therefore, users do not need to know the baudrate of the connected CAN 2.0 device. This is an extremely convenient feature. Baudrates can also be set to a predefined value via rotary switches.


Easily Troubleshoot Communication Issues

It is easy to check if an issue exists on the CAN bus or the Fiber link. The ICF-1171I converters are provided with LEDs that indicate the fiber link state, fiber communication status, CAN bus state, and CAN bus communication status.
ProdGrafik

Specifications

Serial Interface
Optical Fiber 100Base-Fx ports (single-mode/multi-mode ST connector)
Fiber module optical interface    Multi-mode        Single-mode    
Fiber Data Rate 100Base-Fx
Fiber Cable Requirements     62.5/125 μm       9/125 μm   
OM1 OS1
Typical Distance 2 km 40 km
   Wavelength Typical (nm) 1310
TX Range (nm) 1280 to 1340
RX Range (nm) 1100 to 1600
   Optical Power     TX Range (dBm)     -10 to -20      0 to -5
RX Range (dBm) -3 to -32     -3 to -34    
Link Budget (dB) 12 29
   Dispersion Penalty (dB)    3 1
CAN Interface
Isolation 2 kV (built-in)
No. of Ports 1
Signals CAN_L, CAN_H, CAN Signal GND
Terminator N/A, 120 ohms (by DIP)
Protocols CAN 2.0A, CAN 2.0B, CAN FD, compatible with ISO 11898 standard (DIP switch to select CAN 2.0/CAN FD setting)
Fiber Interface
No. of Ports 1
Connector ICF-1171I-S-ST/ ICF-1171I-S-ST-T: Single-mode ST connector
ICF-1171I-M-ST/ ICF-1171I-M-ST-T: Multi-mode ST connector
Optical Fiber Single-mode, typical distance 40 km
Multi-mode, typical distance 2 km
Power Parameters
Input Current 188.5 mA (max.)
Input Voltage 12 to 48 VDC
No. of Power Inputs 2
Power Connector Terminal block
Relays
Contact Current Rating Resistive load: 1 A @ 30 VDC
Pinouts NC, COM, NO
Physical Characteristics
Housing Metal
IP Rating IP30
Dimensions 30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in)
Weight 294 g (0.65 lb)
Installation DIN-rail mounting, Wall mounting (with optional kit)
Environmental Limits
Operating Temperature ICF-1171I-S-ST, ICF-1171I-M-ST: 0 to 60°C (32 to 140°F)
ICF-1171I-S-ST-T, ICF-1171I-M-ST-T: -40 to 75°C (-40 to 167°F)
Storage Temperature (package included) -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Standards and Certifications
EMC EN 55032/35
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV
IEC 61000-4-5 Surge: Power: 2 kV, Signal: 2 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
IEC 61000-4-8 PFMF
International Approval KC
Safety UL 62368-1, EN 62368-1
Vibration IEC 60068-2-6
MTBF
Time 2,412,885 hrs
Standards Telcordia (Bellcore), GB
Warranty
Warranty Period 5 years

Ordering Information

Model Name   Operating Temp.      Fiber Module Type   
ICF-1171I-S-ST 0 to 60°C Single-mode ST
ICF-1171I-S-ST-T -40 to 75°C2 Single-mode ST
ICF-1171I-M-ST 0 to 60°C Multi-mode ST
ICF-1171I-M-ST-T     -40 to 75°C Multi-mode ST



Accessories (sold separately)

    Mounting Kits

      WK-30-02
      Wall-mounting kit, 2 plates, 4 screws, 30 x 66.8 x 2 mm